This manual provides essential information for the safe and effective installation, operation, and maintenance of your GEYA G2R 2P 63A AC110V Automatic Transfer Switch. Please read this manual thoroughly before installation and use, and retain it for future reference.
安全情報
警告: Electrical shock hazard. Installation and servicing must be performed by qualified personnel only. Disconnect all power sources before working on the switch.
- 定格ボリュームを確認してくださいtage and current of the switch match your application.
- 必ず現地の電気規則および規制に従ってください。
- スイッチが破損していると思われる場合は、スイッチを操作しないでください。
- The input power supply must be connected in the correct phase sequence.
製品終了view
The GEYA G2R Automatic Transfer Switch (ATS) is designed to ensure an uninterruptible power supply by automatically switching between a main power source and a backup power source. It features both automatic and manual operation modes and is suitable for DIN rail mounting.
主な特徴:
- 定格電流: 63A
- 定格巻tage: 交流110V
- デュアルモード操作: 自動と手動
- 高速スイッチング: Millisecond-level transfer time (within 50ms)
- 取り付け: DIN Rail and Screw Mounting System
- 材料: High-quality PA6 material with 94V-2 flame retardant grade
製品寸法:

画像: 正面と側面 views of the GEYA G2R Automatic Transfer Switch with detailed dimensions in millimeters. The unit measures 108mm in height, 50.5mm in width (2P version), and 70mm in depth.
セットアップとインストール
The GEYA G2R ATS supports both DIN rail mounting and screw mounting for flexible installation. Ensure the mounting location is dry, well-ventilated, and free from excessive vibration.
配線手順:
Refer to the wiring diagram below for correct connection. It is crucial that the input power supply is connected in the correct phase sequence.

Image: Detailed wiring diagram for the GEYA G2R ATS. It illustrates connections for backup power neutral wire (1), common power neutral wire (2), common power supply (3), backup power supply (4), load power (5), load output neutral wire (6), DIN-Rail buckle (7), backup power live wire (8), common power live wire (9), closing indication (10), manual operation handle (11), and load output live wire (12). A note emphasizes correct phase sequence for input power.
巻tage選択:
適切な巻を選択してくださいtage model for your system. This model is designed for AC 110V systems. Using an incorrect voltage can damage the control circuit.

画像: Voltage selection guide for GEYA G2R ATS. It shows two configurations: G2R-2P-63A-220V for 220/400V systems or one L line 220V, and G2R-2P-63A-110V for 110/220V systems or one L line 110V. A warning advises choosing the correct voltage to prevent coil damage.
操作手順
動作モード:
- 自動モード: The switch automatically detects power failures in the main source (I) and transfers the load to the backup source (II) within 50 milliseconds. When the main power is restored, it automatically switches back.
- 手動モード: Use the manual operation handle to select and switch between power sources I and II.
インジケーターライトのステータス:
- When the power supply is under voltageまたはovervoltage, the indicator light flashes (flashes every two seconds).
- When the power is cut off, the indicator light goes out.
- Green indicator light constantly on: Main power supply is active.
- Red indicator light constantly on: Backup power supply is active.
操作デモンストレーションビデオ:
Video: This video demonstrates the operation of the GEYA ATS, showing how to switch between manual and automatic modes, and how the device automatically transfers power when the main supply is interrupted or restored. It illustrates the indicator light behavior during different power states.
メンテナンス
The GEYA G2R ATS is designed for durability with a mechanical life of ≥8000 times and an electrical life of ≥1500 times. Regular maintenance is minimal but important for optimal performance.
- すべての配線接続が安全で腐食がないことを確認するために定期的に点検してください。
- ユニットを清潔に保ち、ほこりや破片がないようにしてください。
- Test the automatic transfer function periodically by simulating a main power failure (if safe to do so and with appropriate precautions).
トラブルシューティング
| 問題 | 考えられる原因 | 解決 |
|---|---|---|
| スイッチは自動的に転送されません。 | Incorrect mode selection (manual instead of auto). 電源に障害があります。 Control circuit issue. | Ensure the switch is set to "Auto" mode. Check both main and backup power sources. Consult qualified electrician. |
| インジケーターライトが機能しない。 | ユニットに電源が供給されていません。 LED故障。 | Verify power supply connections. Contact support if power is present but lights are off. |
| オーバーボルtage / Undervoltage indication (flashing light). | 入力ボリュームtage outside normal operating range. | Check the stability of your power sources. The unit will automatically recover after 30 seconds if voltag正常に戻ります。 |
仕様
| パラメータ | 価値 |
|---|---|
| 定格電流 | 63A |
| 定格断熱材Voltage | 690V |
| 定格巻tage | 交流110V |
| 定格周波数 | 50/60Hz |
| Rated Short-Circuit Current | 5KA |
| 機械生命 | ≥8000回 |
| 電気寿命 | ≥1500回 |
| 難燃性グレード | 94V-2 |
| 取り付けタイプ | DINレールマウント |
| Number of Poles | 2 |
| 商品型番 | IG-G2R-2P-63A-AC110V |
| パッケージ寸法 | 4.84 x 3.43 x 2.2 インチ; 13.44 オンス |
保証とサポート
保証情報や技術サポートについては、メーカーの公式ウェブサイトをご覧ください。 webご購入いただいた販売店にお問い合わせいただくか、保証請求の際に購入レシートを保管してください。