1. はじめに
The SmartGen HAT560NB ATS Controller is an intelligent dual-supply module designed for Automatic Transfer Systems (ATS). It integrates digital, intelligent, and networked functionalities to provide precise voltage measurement and control for various power supply configurations. This controller is suitable for specialized ATS, Contactor ATS, and Air Break ATS applications, offering a compact structure, advanced circuitry, and high reliability.
It is engineered to reduce operational errors through automatic measurement and control, making it an ideal solution for managing power transfer between different sources like mains and generators.

図1: 前面 view of the SmartGen HAT560NB ATS Controller, showing the LCD display and operational buttons.
2. Features and Characteristics
The HAT560NB controller incorporates a powerful microprocessor for accurate monitoring and control. Key features include:
- System type configuration: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
- 132x64 LCD with backlight, offering optional Chinese and English display with push-button operation.
- Measurement and display of 2-way 3-phase voltage と周波数。
- 過剰/不足ボラティリティに対する保護tage, loss of phase, reverse phase sequence, and over/under frequency.
- Automatic and Manual operating modes. Manual mode allows forced switch closure or opening.
- All parameters are configurable on-site, secured by two different passwords for authorized access.
- Genset commissioning can be set to On-load or Off-load mode.
- Automatic re-closing function for the ATS Controller.
- Configurable closing output signal as either on intervals or continuous output.
- Applicable for ATS with one neutral position, two neutral positions, and non-position types.
- Monitors 1-3 phase AC mains voltages。
- Manages changeover of both generator and mains contactors.
- Sends remote start commands to the generating set.
- Compatible with various contactors and changeover switch types.
3. セットアップとインストール
Proper installation is crucial for the safe and reliable operation of the HAT560NB controller. Ensure all power is disconnected before beginning installation. Refer to the wiring diagrams and terminal descriptions for correct connections.
3.1 配線図
The HAT560NB controller supports various wiring configurations depending on the ATS type. Below are typical wiring diagrams for different setups. Always consult a qualified electrician for installation.

Figure 2: Comprehensive wiring diagrams illustrating connections for ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG ATS controller types. These diagrams show connections for 1# and 2# power supplies, load, and remote start signals.

Figure 3: Additional wiring diagrams focusing on SGQ-N/T, SGQ-M, and Contactor ATS configurations, detailing input and output connections for the controller.
3.2 接続端子
The controller features clearly labeled terminals for power input, auxiliary outputs, and control signals. Ensure each wire is securely connected to its designated terminal.

図4:背面 view of the HAT560NB controller, displaying the layout and labeling of all connecting terminals, including power inputs, auxiliary outputs, and communication ports.
4. 操作手順
The HAT560NB controller offers both automatic and manual operation modes, accessible via its front panel buttons and LCD display.
4.1 電源投入と初期表示
Upon powering on, the LCD will display system information, including voltage and frequency readings for both power sources. The backlight ensures visibility in various lighting conditions.
4.2 モード選択
- 自動モード: The controller automatically monitors the power sources and initiates transfer based on pre-set parameters and detected abnormalities (e.g., over/under voltage, frequency deviations, phase loss).
- 手動モード: Allows the user to manually control the opening or closing of the transfer switches. This mode is typically used for testing or specific operational requirements.
4.3パラメータ設定
All operational parameters can be configured directly on the unit using the push-buttons and LCD interface. Access to parameter settings is protected by a two-level password system to prevent unauthorized changes. Refer to the detailed programming guide (not included in this manual) for specific parameter definitions and adjustment procedures.
5. メンテナンス
Regular maintenance ensures the longevity and reliable performance of your HAT560NB ATS Controller.
- クリーニング: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Avoid abrasive cleaners or solvents.
- 接続チェック: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to intermittent operation or system failures.
- 環境条件: 内部コンポーネントの損傷を防ぐために、動作環境が指定された温度と湿度の範囲内であることを確認してください。
内部のメンテナンスや修理については、資格のあるサービス担当者にお問い合わせください。
6。 トラブルシューティング
This section provides guidance on common issues you might encounter with the HAT560NB controller.
| 問題 | 考えられる原因 | 解決 |
|---|---|---|
| コントローラーの電源が入らない | No DC power supply; Incorrect wiring | Check DC 8.0V-35.0V power supply connections; Verify wiring according to diagrams. |
| ATS not transferring automatically | Automatic mode not selected; Fault detected on active power source (e.g., over/under voltage, frequency); Incorrect parameters | Ensure controller is in Automatic mode; Check power source status; Verify parameter settings. |
| Display shows error for voltage /頻度 | Actual power source issue; Sensor/input wiring problem | 実際のボリュームを確認するtage and frequency of the power source; Inspect AC voltage入力配線。 |
| ボタンが反応しない | Temporary software glitch; Hardware issue | Restart the controller by cycling power; If issue persists, contact support. |
7. 仕様
The following table details the technical specifications for the SmartGen HAT560NB ATS Controller.

Figure 5: Detailed specifications table for the HAT560N series ATS Controller, including operating voltage, power consumption, AC voltage input ranges, rated frequency, relay outputs, communication, dimensions, and environmental conditions.
| アイテム | 仕様 |
|---|---|
| 営業巻tage | DC 8.0V-35.0V (continuous power supply) |
| ACVol。tage入力 | AC170V-270V (during AC power L1N1/L2N2 supply) |
| 消費電力 | <3W (スタンバイモード: <2W) |
| 定格周波数 | 50/60Hz |
| リレー出力を閉じる | 16A AC250V (Volts free output) |
| 補助リレー出力1 | 7A AC250V (Volts free output) |
| 補助リレー出力2 | 7A AC250V (Volts free output) |
| 補助リレー出力3 | 16A AC250V (Volts free output) |
| 補助リレー出力4 | 16A AC250V (Volts free output) |
| デジタル入力 | GND connect is active |
| コミュニケーション | LINKインターフェース、MODBUSプロトコル |
| ケース寸法 | 139mm x 120mm x 48mm(5.47 x 4.72 x 1.89インチ) |
| パネルカットアウト | 130mm×111mm |
| 労働条件 | Temperature: (-25~+70)°C, Humidity: (20~93)%RH |
| 保管条件 | 温度: (-25~+70)°C |
| 保護レベル | IP55ガスケット |
| 絶縁強度 | AC2.2kV vol を適用tagハイボリューム間tage端子と低音量tage端末; 漏れ電流は 3 分間で 1mA 以下です。 |
| 重さ | 0.62kg(1.63ポンド) |